EasyManuals Logo
Home>Toshiba>Inverter>TOSVERT VF-S15 series

Toshiba TOSVERT VF-S15 series User Manual

Toshiba TOSVERT VF-S15 series
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #41 background imageLoading...
Page #41 background image
E6581913
40
5.3. Error codes
In case of the following errors, the return commands from the inverters are added 80h to the com-
mands received by the inverters. The following error codes are used.
Error Code Description
01
- Command error
- Function code 43 supported but MEI Type not equal to 14
02
- Communication number error
- It tried to write to parameter with only reading.
03
- Data range error
- Fixed-data error
- Function code 43 and MEI Type 14 supported but invalid Read Device ID Code
(Read Device ID code > 3)
04
- Unable to execute
- Writing in write-disable-during-operation parameter
- Writing in parameter that is executing TYP
- F700 (Parameter protection selection) is 2:Writing prohibited (RS485), 4:Writing
and Reading prohibited (RS485)
- If F738 (Password setting) was set to data, F738 can not set to data.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com

Table of Contents

Other manuals for Toshiba TOSVERT VF-S15 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S15 series and is the answer not in the manual?

Toshiba TOSVERT VF-S15 series Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-S15 series
CategoryInverter
LanguageEnglish

Related product manuals