EasyManuals Logo
Home>Trane>Controller>Tracer AH540

Trane Tracer AH540 User Manual

Trane Tracer AH540
134 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
Timed override control
CNT-SVX05B-EN 47
Timed override control
This sequence applies to both space temperature control and discharge
air temperature control, with differences as noted.
If the zone sensor has a timed override option (
ON/CANCEL buttons), push-
ing the
ON button initiates a timed override request. A timed override
request changes the occupancy mode from unoccupied mode to occupied
bypass mode. In occupied bypass mode, the controller controls the zone
temperature based on the occupied heating or cooling setpoints. The occu-
pied bypass time, which resides in the Tracer AH540/541 and defines the
duration of the override, is configurable from 0 to 240 minutes. The
default value is 120 minutes for space temperature control; the default
value is 0 minutes (disabled) for discharge air temperature control. When
the occupied bypass time expires, the unit transitions from occupied
bypass mode to unoccupied mode. Pushing the
CANCEL button cancels the
timed override request. A timed override cancel request will end the
timed override before the occupied bypass time has expired and will tran-
sition the unit from occupied bypass mode to unoccupied mode.
If the controller is in any mode other than unoccupied when the
ON but-
ton is pressed, the controller still starts the occupied bypass timer with-
out changing the mode to occupied bypass. If the controller is placed in
unoccupied mode before the occupied bypass timer expires, the controller
will be placed in occupied bypass mode and remain in that mode until
either the
CANCEL button is pressed on the Trane zone sensor or the occu-
pied bypass time expires.
Morning warm-up
The morning warm-up function initiates a special heating sequence to
raise space temperature to occupied conditions. This sequence is espe-
cially useful for a building occupancy transition from unoccupied to occu-
pied.
The Tracer AH540/541 controller operates this sequence according to the
configured control mode.
Space temperature control: Morning warm-up
The controller keeps the outdoor air damper closed (when a mixing box is
present) anytime during a occupied, occupied bypass, or occupied standby
mode when the space temperature is 3ºF or more below the heating set-
point. The damper remains closed indefinitely (no time limit). As the
space temperature increases above this threshold, the outdoor damper
progressively opens toward the minimum position setpoint. When the
space temperature is within 2ºF of the effective heating setpoint, the out-
door air damper will be at the minimum position setpoint.
The outdoor air damper normally is open to a minimum position during
the occupied mode when the controller turns On the supply fan. The
damper normally is closed during:

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Tracer AH540 and is the answer not in the manual?

Trane Tracer AH540 Specifications

General IconGeneral
BrandTrane
ModelTracer AH540
CategoryController
LanguageEnglish

Related product manuals