EasyManuals Logo
Home>Trane>Controller>Tracer AH540

Trane Tracer AH540 User Manual

Trane Tracer AH540
134 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #58 background imageLoading...
Page #58 background image
Chapter 4 Sequence of operation
48 CNT-SVX05B-EN
Warm-up/cool-down mode
Unoccupied mode
Certain diagnostic conditions
Low ambient damper lockout
Anytime the supply fan is Off
Morning warm-up can also be a communicated request from a Trane
Tracer Summit building automation system. When the Tracer AH540/541
controller receives a communicated morning warm-up request, heating
mode is enabled and the outdoor air damper closes. The controller
remains in morning warm-up until a different request is communicated.
Discharge air temperature control: Morning warm-up
If the controller is configured for discharge air temperature control, the
controller requires a space temperature input (hard-wired or communi-
cated) and setpoint input (local, communicated, or default value) to ini-
tiate the morning warm-up sequence of operation. The space temperature
and setpoint inputs are used by the controller to determine if heating or
cooling air should be supplied to the space.
On a transition from unoccupied to occupied, occupied bypass, or occupied
standby, the controller compares the space temperature to the heating
setpoint. If the space temperature is 1.5°F below the heating setpoint,
morning warm-up is initiated. The outdoor air damper closes (or remains
closed) and heat/cool mode is heating.
The morning warm-up control sequence has no time limit upon a transi-
tion from unoccupied to occupied, when the controller is configured for
discharge air temperature control.
Morning warm-up can also be a communicated request from a building
automation system. When the Tracer
AH540/541 controller receives a
communicated morning warm-up request, heating mode is enabled and
the outdoor air damper closes. The controller remains in morning warm-
up until a different request is communicated.
Daytime warm-up
This sequence applies to controllers configured for discharge air tempera-
ture control. The air-handling units must have heating capacity (hydronic
or steam) and a communicated or wired space temperature must exist.
Daytime warm-up allows the controller to automatically change to heat-
ing if the space temperature is below the effective heating setpoint by a
temperature that is more than the configured daytime warm-up enable
differential. Daytime warm-up coordinates the controller heat/cool to
heating, as well as communicates the controller mode of operation to the
duct system for changeover.
The daytime warm-up start setpoint is a configurable temperature below
the effective space heating setpoint. When the space temperature drops to

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane Tracer AH540 and is the answer not in the manual?

Trane Tracer AH540 Specifications

General IconGeneral
BrandTrane
ModelTracer AH540
CategoryController
LanguageEnglish

Related product manuals