Do you have a question about the Watts Aerco Benchmark Series and is the answer not in the manual?
General safety advisories and installation compliance requirements.
Procedures for immediate shutdown in emergencies.
Instructions for taking the boiler out of service for extended periods.
Specific installation requirements for Massachusetts.
Overview of accessing the Edge Controller functionality.
Details on accessing the controller with different security levels.
Guide to starting the boiler using the Edge Controller.
Steps involved in the pre-purge and ignition sequence.
Air/Fuel Valve positions for starting and stopping the unit.
Relationship between Air/Fuel Valve position and energy input.
Air/Fuel Valve position vs. energy input for BMK 750/1000.
Air/Fuel Valve position vs. energy input for BMK 1500.
Air/Fuel Valve position vs. energy input for BMK 2000.
Air/Fuel Valve position vs. energy input for BMK 2500.
Air/Fuel Valve position vs. energy input for BMK 3000.
Air/Fuel Valve position vs. energy input for BMK 5000.
Air/Fuel Valve position vs. energy input for BMK 6000.
Prerequisites and essential steps for initial boiler startup.
Necessary tools and instrumentation for performing combustion calibration.
Information on fuel types and the importance of combustion calibration.
Procedure for calibrating the boiler's combustion for optimal performance.
Step-by-step instructions for natural gas combustion calibration.
Step-by-step instructions for propane gas combustion calibration.
Steps for reassembling the unit after calibration.
Instructions for switching between natural gas and propane fuels.
Explanation of automatic and manual reset over-temperature limit controls.
Procedure to adjust the automatic reset limit switch temperature.
Procedure to reset the manual reset limit switch after an alarm.
How to switch temperature display between F and C.
Importance and general procedures for testing safety devices.
Procedure to simulate and test a low gas pressure fault.
Testing low gas pressure for BMK 750-2500 units.
Testing low gas pressure for BMK 3000-6000 units.
Procedure to simulate and test a high gas pressure fault.
Testing high gas pressure for BMK 750-2500 units.
Testing high gas pressure for BMK 3000-6000 units.
Steps to simulate and test a low water level fault condition.
Simulating and testing high water temperature faults.
Testing various interlock circuits for proper operation.
Testing the remote interlock circuit.
Testing the delayed interlock circuits.
Simulating and testing flame fault conditions.
Testing the blower proof and blocked inlet switches.
Procedure to test the blower proof switch.
Procedure to test the blocked inlet switch.
Checking the SSOV proof of closure switch functionality.
Testing the purge switch during the purge cycle.
Testing the ignition switch during the ignition cycle.
Testing the safety pressure relief valve.
Operation based on outside air temperatures to adjust supply header temperature.
Mounting and connection instructions for the outdoor air sensor.
Steps to set up and start the unit in Outdoor Reset mode.
Mode for maintaining a fixed header temperature.
Remotely controlling the unit's setpoint via EMS or BAS.
Changing air/fuel valve position via remote signal from EMS or BAS.
System for operating multiple units efficiently via RS-485 network.
System using multiple boilers for space heating and domestic hot water.
Wiring instructions for ACS, ACS Relay Box, and I/O Box.
Setup and startup procedures for the Combination mode.
Overview of the Boiler Sequencing Technology system.
Notes regarding ProtoNode installation for BST systems.
Chart to select BST installation options and corresponding instructions.
Instructions for implementing BST configurations.
BST Option 1: Direct wired header sensor setup.
BST Option 2: Modbus wired header sensor setup.
BST Option 3: Direct wired header and outdoor sensor setup.
BST Option 4: Modbus header and outdoor sensor setup.
BST Option 5: Direct wired header and 4-20mA setpoint drive.
BST Option 6: Direct wired header and Modbus setpoint drive.
BST Option 7: Modbus header and 4-20mA setpoint drive.
BST Option 8: Modbus header and Modbus setpoint drive.
Schedule of recommended routine maintenance tasks and frequencies.
Maintenance procedures for the igniter-injector assembly.
Inspection and replacement of the pilot ignition rod.
Inspection and replacement of the flame detector.
Cleaning and inspection of the O2 sensor for accuracy.
Maintenance and troubleshooting for the air pump in the air eductor assembly.
Importance of testing safety devices as per codes.
Inspection of the burner assembly for intactness and function.
Inspection and cleaning of the condensate drain trap for proper flow.
Maintenance schedule for cleaning or replacing the air filter.
Replacement of refractory materials in the combustion chamber.
Step-by-step instructions for replacing the rear refractory.
Instructions for replacing the front refractory material.
Procedures for taking the boiler out of service for one year or more.
Instructions for storing Benchmark 5000/6000 blowers long-term.
Procedures for putting the boiler back into service after prolonged shutdown.
Recommended schedule and actions for periodic testing of boiler controls and safety devices.
List of recommended emergency and optional spare parts.
Introduction to the AERtrim system for optimizing air-fuel ratios.
Instructions for activating the AERtrim function with an activation code.
Details on how the AERtrim system adjusts blower voltage for optimal combustion.
Automatic calibration feature to maintain O2 sensor accuracy.
Default and adjustable menu values for AERtrim settings.
Maintenance and troubleshooting for the AERtrim system, focusing on the O2 sensor.
Introduction to isolating and correcting boiler faults.
Troubleshooting faults that do not display specific messages.