Benchmark Platinum-Edge: Operation-Service Manual
SECTION 4 – INITIAL START-UP
OMM-0137_D • GF-211 • 7/16/2019 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page 35 of 146
Figure 4-1e: Port Location for Combustion Calibration – BMK 5000-6000
4.2.3 Accessing the Analyzer Probe Port
Benchmark units contain a 1/4” NPT port on the side of the exhaust manifold, as shown in
Figure 4-2. Prepare the port for the combustion analyzer probe as follows:
Analyzer Probe Port Access Instructions
1. Refer to Figure 4-2 and remove the 1/4” NPT plug from the exhaust manifold.
2. If necessary, adjust the stop on the combustion analyzer probe so it will extend mid-way
into the flue gas flow. DO NOT install the probe at this time.
Figure 4-2: Analyzer Probe Port Location (BMK 1500 shown)
WATER INLET
PORT
SHUT-OFF
DETECTION BALL VALVE
(Install manometer here for
downstream combustion
calibration reading)
(Install manometer here for
upstream combustion calibration
reading)
manometer if hose
barb is preferred
PRESSURE SWITCH