Benchmark Platinum-Edge: Operation-Service Manual
SECTION 5 SAFETY DEVICE TESTING
OMM-0137_D • GF-211 7/16/2019 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 63 of 146
5.5 WATER TEMPERATURE FAULT TEST
A high water temperature fault is simulated by adjusting the Automatic Reset Over-
Temperature switch.
Water Temperature Fault Test Instructions
1. Start the unit in the normal operating mode and allow the unit to stabilize at its setpoint.
2. On the Automatic Reset Over-Temperature switch, note the current setting, then:
a. Press the Set button two times, to activate a setting change.
b. Use the Down arrow to lower the setting to a temperature below the Outlet
temperature displayed on the Controller’s front face (see Figure 5-5b).
c. Press the Set and Down arrow at the same time to save that temperature setting.
Figure 5-5a: Over Temperature Limit Switches
NOTE:
If the Controller’s is not configured to display outlet temperature, go to the Main Menu
Advanced Setup Unit Front Panel Configuration screen and set the Upper-Right
Display parameter to Water Outlet.
Figure 5-5b: Edge Controller Front Face
3. Once the Automatic Reset Over-Temperature switch setting is approximately just below
the actual outlet water temperature, the unit should shut down, the FAULT indicator should
start flashing, and a High Water Temp Switch Open fault message should be displayed. It
should not be possible to restart the unit.
4. Repeat Step 2 to return the Automatic Reset switch, but press the Up arrow to it to its
original setting.
5. The unit should start once the setting is above the actual outlet water temperature.
6. Repeat steps 1 4 on the Manual Reset switch. However, unlike the Automatic Reset
switch, the unit will not restart automatically when the original temperature is restored. You
must press the RST (Reset) button to restart the unit.
OUTLET
TEMPERATURE
INDICATOR
OUTLET
TEMPERATURE
AUTOMATIC
RESET
SWITCH
MANUAL
RESET
SWITCH
TEMPERATURE ADJUSTMENT CONTROLS

Table of Contents

Other manuals for Watts Aerco Benchmark Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Watts Aerco Benchmark Series and is the answer not in the manual?

Watts Aerco Benchmark Series Specifications

General IconGeneral
BrandWatts
ModelAerco Benchmark Series
CategoryBoiler
LanguageEnglish

Related product manuals