EasyManuals Logo
Home>Watts>Boiler>Aerco Benchmark Series

Watts Aerco Benchmark Series User Manual

Watts Aerco Benchmark Series
146 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #89 background imageLoading...
Page #89 background image
Benchmark Platinum-Edge: Operation-Service Manual
SECTION 7 BOILER SEQUENCING TECHNOLOGY
OMM-0137_D • GF-211 7/16/2019 Technical Support (800) 526-0288 Mon-Fri, 8 am - 5 pm EST Page 89 of 146
7.3.4 Option 4 Outdoor Reset: Modbus Header Sensor & Modbus
Outdoor Sensor
OPTION 4
Instructions: Outdoor Reset, Modbus Header Sensor & Modbus Outdoor Sensor
NOTE:
Both Header Sensor AND Outdoor Sensor must be wired. See the Edge Controller Manual
and (OMM-0139, GF-213) for more information.
Step 1: HEADER SENSOR WIRING ANY BOILER
1. Connect the Modbus Transmitter (P/N 65169) terminal Pin B to the I/O Board strip J3,
terminal 13 (BST RS485+) and Pin A to terminal 15 (BST RS485) on any of the Boiler
units using Shielded pair 18 - 22 AWG cable.
2. Using Shielded pair 18 - 22 AWG cable, connect the Header Temperature Sensor (P/N
24410) to pins 2 and 3 of the Modbus Transmitter.
3. Install a jumper wire between pins 1 and 2 of the Modbus Transmitter.
NOTES:
Polarity must be observed for the RS485 connections.
Ground the shield to any Shield terminal on the I/O Board, such as Terminal 3 or 8.
The Header Sensor must be installed between 2 and 10 feet (0.61 and 3.1m)
downstream of the LAST boiler in the plant’s supply water header.
There is no polarity to be observed. The ground for the shield is at the power supply
ground. The sensor end of the shield must be left free and ungrounded.
Step 2: OUTDOOR SENSOR WIRING
1. If you have not already done so, complete step 1 of the instructions above to connect the
Modbus Transmitter to the I/O Board.
2. Connect the Outdoor Temperature Sensor (P/N 61048) to Pins 5 and 6 of the Modbus
Transmitter using a Shielded pair 18 - 22 AWG cable.
3. Install a jumper wire between Pins 4 and 5 on the Modbus Transmitter.
MODBUS TRANSMITTER
15 BST RS485
HEADER TEMP SENSOR
(P/N 24410)
13 BST RS485+
3 Shield
I/O BOARD STRIP J3
15 BST RS485
13 BST RS485+
3 Shield
MODBUS TRANSMITTER
OUTDOOR TEMP SENSOR
(P/N 61048)
I/O BOARD STRIP J3

Table of Contents

Other manuals for Watts Aerco Benchmark Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Watts Aerco Benchmark Series and is the answer not in the manual?

Watts Aerco Benchmark Series Specifications

General IconGeneral
BrandWatts
ModelAerco Benchmark Series
CategoryBoiler
LanguageEnglish

Related product manuals