VB5N series inverter
30
4 Function Parameters
4-1. Function code
○: Parameters can be changed while running
×: Parameters can not be changed while running
*: Parameters can only be read, can not be changed
1. Basic running parameters (Group P0)
Group P0: Basic running parameters
1: open-loop vector control
(VB5N inverter no this function)
0: potentiometer on the panel
1: Increase/Decrease key
2: digital setting 1, via keys on the
panel
3: digital setting 2, via terminal
UP/DOWN
4: digit setting 3, via serial port
5: VI analog input (VI-GND)
6: CI analog input (CI-GND)
7: Pulse input (PULSE)
8: Combined setting mode (refer
to P3.00)
P0.19 max frequency ~ P0.20 min
frequency limit
Running command
selection
1: Teminal
2: serial port
Running direction
setting
0: jog forward via panel
1: jog reverse via panel
Ten bit:
0: enable to reverse running
1: prohibit reverse running
Run forward/reverse
dead zone time
Cut-off frequency
for torque boost
0.00Hz~basic running frequency
P0.07
10.0%~50.0% (Acc/Dec time)