VB5N series inverter
53
The relationship between CI and setting frequency:
The relationship between PULSE and setting frequency:
4-2-3. Starting and braking parameters (Group P2)
0: Start from the starting frequency
Inverter starts at the starting frequency (P2.01) within the lasting time of starting frequency (P2.02).
1: Brake first and then start from the starting frequency
Brake with DC braking current (P2.03) within braking time (P2.04) and then start at starting frequency.
2: Track the speed then start
When P2.00=2, it is valid for repowering after instantaneous power off or restarting after external fault. As shown in
Fig.4-9.
A:PULSE setting Amin:min setting Fmin:frequency of min setting
Amax:max setting Fmax:frequency of max setting
A:CI set frequency Amin:min setting Fmin:frequency of min setting
Amax:max setting Fmax:max frequency of max setting