EasyManuals Logo
Home>Xinje>Inverter>VB5N Series

Xinje VB5N Series User Manual

Xinje VB5N Series
105 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #62 background imageLoading...
Page #62 background image
VB5N series inverter
54
Fig.4-9 Speed track then start
Note: (1) Starting mode 0: It is recommended for general application or when the inverter drives synchromous motor.
(2) Starting mode 1: It is suitable for small inertial load that motor will forward or reverse rotate without load and it
is not recommended for big inertial load.
(3) Starting mode 2: It is suitable for motor startin during free stop or restarting after instantaneous power off.
P2.01
Starting frequency
Range: 0.20~20.00Hz
0.50 Hz
P2.02
Lasting time of starting frequency
Range: 0.0~30.0S
0.0S
Starting frequency points to the initial frequency when inverter starts; see Fig.4-10 Fs. Lasting time of starting frequency
points to the time while inverter is running at the starting frequency, see Fig.4-10 t
1.
Note: Starting frequency is not limited by the lowest frequency.
Fig.4-10 Starting frequency and starting time
P2.03
DC brake current when starting
Range: 0~80(%)
0(%)
P2.04
DC brake time when starting
Range: 0.0~60.0s
0.0s
When P2.00 =1, P2.03 and P2.04 are valid, as shown in Fig. 4-11.
The setting of DC brake current is the percentage of rated current. When the starting DC brake time is 0.0s, there is no DC
brake process.
Fmax
Start frequency
Fs
t1 start time
time
Frequency
Power
Motor speed
Output frequency
of inverter
ON OFF ON

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Xinje VB5N Series and is the answer not in the manual?

Xinje VB5N Series Specifications

General IconGeneral
BrandXinje
ModelVB5N Series
CategoryInverter
LanguageEnglish

Related product manuals