EasyManuals Logo
Home>Xinje>Inverter>VB5N Series

Xinje VB5N Series User Manual

Xinje VB5N Series
105 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #40 background imageLoading...
Page #40 background image
VB5N series inverter
32
min setting of CI
P1.09
Max setting of CI
P1.07 ~10.00V
0.01V
10.00V
P1.10
Frequency of the
max setting of CI
0.00~highest frequency
0.01Hz
50.00Hz
P1.11
Max input pulse
frequency of
PULSE
0.1~20.0K
0.1K
10.0K
P1.12
Min setting of
PULSE
0.0~P1.14
(Max setting of PULSE)
0.1K
0.1K
P1.13
Frequency of the
min setting of
PULSE
0.00~highest frequency
0.01Hz
0.00Hz
P1.14
Max setting of
PULSE
P1.12 (Min setting of PULSE) ~ P1.11
(Max input frequency)
0.1K
10.0K
P1.15
Frequency of the
max setting of
PULSE
0.00~highest frequency
0.01Hz
50.00Hz
P1.16
Input mode of CI
0: 4~20mA
1: 0~10V
-
0
3. Starting and Braking Prameters (Group P2)
Group P2: Starting and Braking Prameters
Parameter
Name
Range
Minmum
unit
Factory setting
Change
P2.00
Starting mode
0: Start from the starting
frequency
1: Brake first and then start
from the starting frequency
2: detect current speed then
startup
1
0
×
P2.01
Starting frequency
0.20~20.00Hz
0.01Hz
0.50Hz
P2.02
Holding time of starting
frequency
0.0~30.0s
0.1s
0.0s
P2.03
DC brake current when
startup
0.0~80.0%
0.1%
0%
P2.04
DC brake time when startup
0.0~60.0s
0.1s
0.0s
P2.05
Stopping mode
0: Decelerate
1: Free stop
2: Decelerate + DC brake
1
0
×
P2.06
DC brake startup frequency
when stop
0.0~15.00Hz
0.0Hz
3.00Hz
P2.07
DC brake time when stop
0.0~60.0s
0.1s
0.0s
P2.08
DC brake current when stop
0.0~80.0%
0.1%
0.0%