VB5N series inverter
85
Potential energy load or big inertia load
Increase the brake power of external brake unit
Over-voltage
when constant speed
running
Increase the Acc/Dec time
Abnormal change of input voltage
Connect suitable braking unit
Inverter power supply
over-voltage
Check input power or ask for service
Clean the duct and improve ventilation condition
Ambient temperature too high
Improve ventilation condition and decrease carrier fre-
quency
DC braking current is too big
Reduce DC braking current and increase braking time
V/F curve is not suitable
Adjust V/F curve and torque boost value
Restart the motor when it is running
Set to restart after speed detection
Low AC power supply voltage
Select higher power inverter
V/F curve is not suitable
Adjust V/F curve and torque boost value
Common motor is running with heavy load at
low speed for a long time
Please choose frequency conversion motor
Unsuitable motor overload protection coeffi-
cient
Set motor overload protection coefficient correctly
The motor is blocked or the load change too
much
Under-voltage when
running
Too low AC power supply voltage
Check AC power supply voltage
Inverter module pro-
tection
Instant over current of inverter
Refer to solution of over current
3-phase output is short together or ground short
Duct is blocked or fan is damaged
Clean the duct or change the fan
Ambient temperature is too high
Reduce environment temperature
Wires or connectors of control board are loose
Current waveform distorted due to output phase
loss
Auxiliary power is damaged and inverter volt-
age is low
Ask factory or agent for service
Ask factory or agent for service
Peripheral equipment
fault
Emergency stop terminal of peripheral equip-
ment is close
Solve the external fault and cut off the terminal
Wires or connectors of control board are loose