<8. OPERATION VIA HART CONFIGURATION TOOL (HART 5)>
8-1
IM 01E30D01-01EN
8.
OPERATION VIA HART CONFIGURATION TOOL (HART 5)
ThisChapterdescribesthedevice(AXR)operation
proceduresusingaHARTcongurationTool(such
as FieldMate).
NOTE
For more details regarding the operations for
theHARTcongurationtool,readtheHART
congurationtooloperationsmanual.
Note: HART is a registered trademark of the
FieldComm Group.
8.1 HART Protocol Revision
For the models with the output signal code “-J”,
HART protocol revision 5 or 7 is selectable. The
protocolrevisionissetasspeciedintheorder.
Howtoconrmprotocolrevisionisshownbelow.
Therearetwowaystoconrmtheprotocolrevision
set to the transmitter.
(1)Conrmationbythenameplate
The HART protocol revision at the time of
shipment is shown by the last number at the
serial number column of the name plate.
F0801.ai
XXX…XX
5: HART 5
7: HART 7
(2) ConrmationbyusingHARTcongurationtool
Read Subsection 8.8.5.
IMPORTANT
Protocol revision supported by HART
congurationtoolmustbethesameorhigher
than that of the device.
Protcol revision
supported by HART
congurationtool
5 7
Protocol revision of
the device
5
7 ×
: Communication OK
×: Communication NG
NOTE
In this User’s Manual, HART protocol revision
5 and 7 are described as HART 5 and HART 7
respectively.
NOTE
When the output signal code of the device is “-J”,
HART protocol revision can be changed. Read
Subsection 8.8.5 about the procedure of the
revision change of HART 5 and HART 7.
8.2 Device Description (DD) on
aHARTCongurationTool
and AXR Device Revision
8.2.1 DD Revision and Device Revision
BeforeusingtheHARTCongurationTool(such
asFieldMate),conrmthattheDD(Device
Description)oftheAXRisinstalledinthe
CongurationTool.
• AXR:HART5
• Devicetype:0x57
• DeviceRevision:2
• DDRevision:2
TheDDrevisionsforAXRandCongurationTool’s
canconrminaccordancewiththefollowingsteps.
If the correct DD is not installed in the HART
CongurationTool,downloadthemfromtheHART
ofcialsite,otherwise,contacttherespective
vendorsoftheCongurationToolforitsupgrade
information.
1. ConrmationofthedevicerevisionforAXR
(1) ConnecttheCongurationTooltotheAXR.
The device revision can be checked as
follows.
DD DeviceSetup→Review→Review4
→Flddevrev
2. Conrmationofthedevicerevisionforthe
HARTCongurationTool
(1) TurnonthepoweroftheCongurationTool
under the standalone condition.