036-21323-002-C-0206
Unitary Products Group 9
All dimensions are in inches. They are
subject to change without notice. Certi-
fied dimensions will be provided upon
request.
B
A
C
OUTDOOR UNIT DIMENSIONS
Unit
Dimensions (In.)
ABC
15 Ton 37.5 45.75 110.5
20 Ton 37.5 45.75 128.1
TABLE 8: CONNECTIONS
Connection Entry Connection Size
15 Ton
1
1. Refer to Tables 13 and 14 for appropriate suction
and liquid line sizes.
20 Ton
1
Suction Line 1-1/8 ID 1-3/8 ID
Liquid Line 5/8 ID 5/8 ID
Power Wiring 2-1/8 KO 2-1/8 KO
Control Wiring 7/8 KO 7/8 KO
TABLE 9: UNIT CLEARANCES
Location Dimensions
Overhead (Top)
1
1. Units must be installed outdoors. Overhanging structures or
shrubs should not obstruct condenser air discharge.
120”
Front access panels 36”
Left Side 30”
Right Side 30”
Rear 24”
Bottom
2
2. Adequate snow clearance must be provided if winter operation
is expected.
0”
TABLE 10: HB CORNER WEIGHTS AND CENTER OF GRAVITY
UNIT SIZE
SHIPPING
WEIGHT
OPERATING
WEIGHT
ABCD
UNIT
LENGTH
UNIT
WIDTH
DIM X DIM Y
15 Ton Outdoor 944 959 205 275 275 205 110 46 47 23
20 Ton Outdoor 1124 1141 232 339 339 232 128 46 52 23
FIGURE 6 - CORNER WEIGHT
DIM Y
DIM X
LENGTH
WIDTH
A
C
B
D
CG