EasyManuals Logo
Home>ZIEHL-ABEGG>Control Unit>AM-CAN-OPEN

ZIEHL-ABEGG AM-CAN-OPEN User Manual

ZIEHL-ABEGG AM-CAN-OPEN
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #24 background imageLoading...
Page #24 background image
8.3.3 General
MB Holding Register1, Address: h0 = PIN input
MB Holding Register1, Address: h0 PIN input
Code input to execute special functions e.g. default setting
Access / necessary PIN protection level RW /
|
0
|
minimal value 0
maximum value 65535
Default 0
Bit [15:0] Decimal value 0 - 65535
PIN Code Function
3698
Communications parameters take-over
2143
Reset motor controller (approx. 3.2 sec delay)
1234
Release of the PIN protection level
|
1
|
, at programmed PIN
protection level
|
0
|
(
register address: 16 / bits [9:8])
0010
Release of the PIN protection level
|
2
|
, at programmed PIN
protection level
|
0
|
and
|
1
|
(
register address: 16 / bits [9:8])
7401
Reset current maximum value memory
7500 - 7509
Selection events memory 0 up to 9 (content of events memory
place is copied in query i30, i31 register). 7500 is the most
current fault
xxxx
Administrator password (factory conguration)
xxxx
Delete error memory
xxxx
Loading the factory settings:
xxxx
COM Watchdog Reset
xxxx
Code on request from ZIEHL-ABEGG
Information
Without any further action a released PIN protection level is reset automatically to the programmed
PIN protection leval after approximately 15 minutes!
Reset to factory setting is possible only by parameter set download. Each device has a set of
parameters. This is loaded by the factory and can be loaded any time with ZIEHL-ABEGG tools
again.
Operating Instructions AM-CAN-OPEN model series Enclosure
L-BAL-E199-GB 1846 Index 005 Part.-No. 00163405-GB