Section 6 Checking installation
6.1 Identifying hardware and software version
Hardware and software version information can be found from the label that is
attached on the case of the IED. There is also module labels that can be used to
identify modules inside the IED.
6.2 Checking mounting
Check that all fixing screws are tight and that all cables are connected.
6.3 Energizing the IED
Before you connect the auxiliary power, check that the terminal strip is wired and
placed correctly.
During the start-up all LEDs are lit for a short period.
• Green Ready LED starts to flash
• LCD lights up and starting... is displayed
• The main menu is displayed. A steady green Ready LED indicates a successful
start-up.
If the IED detects a diagnostic error during start-up, the green Ready LED flashes
and the internal fault code is displayed on the LCD.
1MRS755958 C Section 6
Checking installation
630 series 63