A.4 Device Redundancy
The following fault conditions cannot be detected in the Linking Device itself and need
to be covered at application level:
a loss of an H1 connection between the primary device and a subset of devices on
an H1 link
a loss of an H1 connection between the secondary device and the entire H1 link or
a subset of devices on an H1 link
Make sure not to permute the H1 terminal blocks. An accidental permutation of the
H1 link connections at the secondary Linking Device will not be detected right away.
On application level, detection will not be possible before a redundancy switch-over
takes place or the live lists of primary and secondary Linking Device are being
compared manually.
2PAA114135-610 96
A Limits and Performance Data
A.4 Device Redundancy

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB Ability 800xA Series and is the answer not in the manual?

ABB Ability 800xA Series Specifications

General IconGeneral
System TypeDistributed Control System (DCS)
ArchitectureClient-server
RedundancySupports redundant controllers, communication networks, and I/O modules
Operating SystemMicrosoft Windows Server
Communication ProtocolsOPC, Modbus, IEC 61850, PROFIBUS, Foundation Fieldbus
IntegrationSupports integration with third-party systems and ABB products
ScalabilityHighly scalable, from small to large installations
CybersecurityBuilt-in cybersecurity features including access control and network security
User InterfaceGraphical user interface
Application SupportSupports a wide range of industrial applications including process control and safety