94 E-Clipse Bypass Configurations for ACH550 Drives
Technical Data
Standard Enclosure Terminals, 500…600 Volt Units
500…600 Volt
Frame
Size
Maximum Wire Size Capacities of Power Terminals
HP Identification
Circuit
Breaker
Disconnect
Switch
Motor
Termination
Ground
Lugs
2 ACH550-BxR-02A7-6 R2
#8
62 in-lbs
#8
7 in-lbs
#6
30 in-lbs
#4
35 in-lbs
3 ACH550-BxR-03A9-6 R2
5 ACH550-BxR-06A1-6 R2
7.5 ACH550-BxR-09A0-6 R2
10 ACH550-BxR-011A-6 R2
15 ACH550-BxR-017A-6 R2
20 ACH550-BxR-022A-6 R3
#1
62 in-lbs
#2
50 in-lbs
#2
50 in-lbs
25 ACH550-BxR-027A-6 R3
30 ACH550-BxR-032A-6 R4
#4
18 in-lbs
#2
120 in-lbs
40 ACH550-BxR-041A-6 R4
50 ACH550-BxR-052A-6 R4
#1
55 in-lbs
60 ACH550-BxR-062A-6 R4
#1
75 in-lbs
75 ACH550-BxR-077A-6 R6
300 MCM
274 in-lbs
#1/0
70 in-lbs
#1
53 in-lbs
3 x #3/0
250 in-lbs
100 ACH550-BxR-099A-6 R6
125 ACH550-BxR-125A-6 R6
300 MCM
275 in-lbs
250 MCM
300 in-lbs
150 ACH550-Bx-R144A-6 R6

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACH550 series and is the answer not in the manual?

ABB ACH550 series Specifications

General IconGeneral
EnclosureIP21, IP55
Output Voltage0 to Supply Voltage
Frequency Range0 to 500 Hz
Control MethodScalar control, vector control
Braking ChopperOptional
CommunicationModbus RTU, Profibus, CANopen, Ethernet
Storage Temperature-40°C to +70°C
Relative Humidity5 to 95 % RH, non-condensing
AltitudeUp to 1000 m (derating above 1000 m)
Cooling MethodAir-cooled