24 ACH550 Installation, Operation and Maintenance Manual
ACH550-UH
Diagnostics
Fault listing
Fault
Code
Fault Name In
Panel
Description and Recommended Corrective Action
1
OVERCURRENT Output current is excessive. Check for and correct:
Excessive motor load.
Insufficient acceleration time (parameters 2202
ACCELER TIME 1 and
2205
ACCELER TIME 2).
Faulty motor, motor cables or connections.
Output disconnect device not interlocked.
Interaction with external input filter.
2
DC OVERVOLT Intermediate circuit DC voltage is excessive. Check for and correct:
Static or transient overvoltages in the input power supply.
Insufficient deceleration time (parameters 2203
DECELER TIME 1 and
2206
DECELER TIME 2).
Verify that overvoltage controller is ON (using parameter 2005).
Interaction with external input filter.
3 DEV OVERTEMP Drive heatsink is overheated. Temperature is at or above limit.
R1…R4 & R7/R8: 115 °C (239 °F)
R5/R6: 125 °C (257 °F)
Check for and correct:
Fan failure.
Obstructions in the air flow.
Dirt or dust coating on the heat sink.
Excessive ambient temperature.
Excessive motor load.
4
SHORT CIRC Fault current. Check for and correct:
A short-circuit in the motor cable(s) or motor.
Supply disturbances.
5RESERVED Not used.
6
DC UNDERVOLT Intermediate circuit DC voltage is not sufficient. Check for and correct:
Missing phase in the input power supply.
Blown fuse.
Undervoltage on mains.
7
AI1 LOSS Analog input 1 loss. Analog input value is less than AI1FLT LIMIT (3021).
Check for and correct:
Source and connection for analog input.
Parameter settings for AI1FLT LIMIT (3021) and 3001 AI<MIN FUNCTION.
8
AI2 LOSS Analog input 2 loss. Analog input value is less than AI2FLT LIMIT (3022).
Check for and correct:
Source and connection for analog input.
Parameter settings for AI2FLT LIMIT (3022) and 3001 AI<MIN FUNCTION.
9
MOT TEMP Motor is too hot, based on either the drive’s estimate or on temperature
feedback.
Check for overloaded motor.
Adjust the parameters used for the estimate (3005…3009).
Check the temperature sensors and Group 35 parameters.