ACH550 Installation, Operation and Maintenance Manual 3
ACH550-UH
Contents
This manual is the Operation and Maintenance Manual for the ACH550 Drives.
Complete technical details and programming information are available in the
ACH550 User’s Manual, publication number 3AUA0000081823.
1. To determine the type of your drive, refer to its construction code on either:
• Serial number label attached on upper part of
the chokeplate between the mounting holes.
• Type code label attached on the heat sink – on
the side of the enclosure.
2. According to the construction code, proceed to your drive’s installation, operation,
diagnostics and maintenance information:
• UH – Below.
• VCR, VDR, BCR, BDR (E-Clipse Bypass) – page 39.
• PCR, PDR (Packaged Drives with Disconnect) – page 79.
ACH550-UH
Installation
Study these installation instructions carefully before proceeding. Failure to observe
the warnings and instructions may cause a malfunction or personal hazard.
WARNING! Before you begin read Safety on page 2.
Note: Keep a minimum of 50 mm (2") of free space on each side and 200 mm (8") of
free space above and below all units from non-heat producing sources. Double
these distances from heat producing sources.
S/N
ACH550-UH-059A-2
2030700001
SW:
V.2.06B
2030700001
Input
Voltage (U1)
Current (I1n)
3 PH 48…63 Hz
200…240 Vac
59.4 A
1 PH 4…63 Hz
200…240 Vac
59.4 A
Output
Voltage (U2)
Current (I2n)
3 PH 0…500 Hz
0…U1 Vac
59.4 A
3 PH 0…500 Hz
0…U1 Vac
28 A
ACH550-UH-059A-2
Power (Pn)
Mfg. Date: 01-December-2005
Org. Firmware: V.2.06B
ABB Inc.
Made in USA of foreign parts
10 HP20 HP
kAIC
S/N
2030700001
Construction
code