162 Parameters
Other [bit] Source selection (see Terms and abbreviations on page 64). -
83.16 Cycles in cleaning
program
Defines the number of cycles performed in cleaning program.
For example, 1 cycle = 1 forward + 1 reverse step.
3
1...65535 Value range
83.20 Cleaning speed
step
Defines the speed/frequency step size in pump cleaning.
Cleaning speed step is same for positive and negative
directions.
Note: If you have disabled the negative rotation direction by
speed limits, the pump cleaning does not operate in the
negative direction.
2400
0...3000 rpm Cleaning speed/frequency value. 1 = 1 rpm
83.25 Time to cleaning
speed
Defines the time required for the drive to reach cleaning
speed set by parameter 83.20 Cleaning speed step.
3.000
0.000...60.000 s Time 1 = 1s
83.26 Time to zero-speed Defines the time required for the drive to reach zero speed
from the cleaning speed set by parameter 83.20 Cleaning
speed step.
3.000
0.000...60.000 s Time 1 = 1s
83.27 Cleaning on time Defines the pump cleaning time in a cycle when the drive is
running at cleaning speed set by 83.20 Cleaning speed step.
10.000
0.000...1000.000 s Time 1 = 1s
83.28 Cleaning off time Defines the cleaning off time when the drive stays at zero
speed between positive and negative pulses and after one
cleaning cycle before starting a new cleaning cycle.
5.000
0.000...1000.000 s Time 1 = 1s
95
95 HW configuration
Various hardware-related settings.
95.01 Supply voltage Selects the supply voltage range. This parameter is used by
the drive to determine the nominal voltage of the supply
network. The parameter also affects the current ratings and
the DC voltage control functions of the drive.
WARNING! An incorrect setting may cause the motor
to rush uncontrollably.
Note: The selections shown depend on the hardware
of the drive. If only one voltage range is valid for the drive in
question, it is selected by default.
Automatic /
not selected
Automatic / not
selected
No voltage range selected. The drive will not start modulating
before a range is selected, unless parameter 95.02 Adaptive
voltage limits is set to Enable, in which case the drive
estimates the supply voltage itself.
0
380…415 V 380…415 V 2
No. Name/Value Description Def/FbEq16
ACQ80 FW.book Page 162 Thursday, February 14, 2019 11:33 AM

Table of Contents

Other manuals for ABB ACQ80-04

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACQ80-04 and is the answer not in the manual?

ABB ACQ80-04 Specifications

General IconGeneral
BrandABB
ModelACQ80-04
CategoryDC Drives
LanguageEnglish

Related product manuals