258 Fieldbus control through a fieldbus adapter
Parameter setting example: FPBA (PROFIBUS)
This example shows how to configure a basic speed control application that uses the
PROFIdrive communication profile with PPO Type 2. The start/stop commands are
according to the PROFIdrive profile and speed control mode.
The table below gives the recommended drive parameter settings.
Direction PZD1 PZD2 PZD3 PZD4 PZD5 PZD6
Out Control word Speed reference Acc time 1 Dec time 1
In Status word Speed actual value Motor current DC voltage
Drive parameter Setting for ACS 560
drives
Description
50.01 FBA A enable 1 = [slot number] Enables communication between the
drive and the fieldbus adapter module.
50.04 FBA A ref1 type 4 = Speed Selects the fieldbus A reference 1 type
and scaling.
50.07 FBA A actual 1 type 0 = Speed or
frequency
Selects the actual value type and scaling
according to the currently active Ref1
mode defined in parameter 50.04.
51.01 FBA A type 1 = FPBA
1)
Shows type of the fieldbus adapter
module.
51.02 Node address 3
2)
Defines the PROFIBUS node address of
the fieldbus adapter module.
51.03 Baud rate 12000
1)
Shows current baud rate on the
PROFIBUS network in kbit/s.
51.04 MSG type 1 = PPO2
1)
Shows telegram type selected by the
PLC configuration tool.
51.05 Profile 0 = PROFIdrive Selects the Control word according to the
PROFIdrive profile (speed control mode).
51.07 RPBA mode 0 = Disabled Disables the RPBA emulation mode.
52.01 FBA data in1 4 = SW 16bit
1)
Status word
52.02 FBA data in2 5 = Act1 16bit Actual value 1
52.03 FBA data in3 01.07
2)
Motor current
52.05 FBA data in5 01.11
2)
DC voltage
53.01 FBA data out1 1 = CW 16bit
1)
Control word
53.02 FBA data out2 2 = Ref1 16bit Reference 1 (speed)
53.03 FBA data out3 23.12
2)
Acceleration time 1
53.05 FBA data out5 23.13
2)
Deceleration time 1
51.27 FBA A par refresh 1 = Configure Validates the configuration parameter
settings.