84 Parameters
12
12 Standard AI
Configuration of standard analog inputs.
12.02 AI force selection The true readings of the analog inputs can be overridden for
eg. testing purposes. A forced value parameter is provided for
each analog input, and its value is applied whenever the
corresponding bit in this parameter is 1.
Note: AI filter times (parameters 12.16 AI1 filter time and
12.26 AI2 filter time) have no effect on forced AI values
(parameters 12.13 AI1 forced value and 12.23 AI2 forced
value).
Note: Boot and power cycle reset the force selections
(parameters 12.02 and 12.03).
0b0000
0b000...0b1111 Forced values selector for ana log i nputs AI1 and AI2. 1 = 1
12.03 AI supervision
function
Selects how the drive reacts when an analog input signal
moves out of the minimum and/or maximum limits specified
for the input.
The inputs and the limits to be observed are selected by
parameter 12.04 AI supervision selection.
No action
No action No action taken. 0
Fault Drive trips on 80A0 AI supervision.1
Warning Drive generates an A8A0 AI supervision warning. 2
Last speed Drive generates a warning (A8A0 AI supervision) and freezes
the speed (or frequency) to the level the drive was operating
at. The speed/frequency is determined on the basis of actual
speed using 850 ms low-pass filtering.
WARNING! Make sure that it is safe to continue
operation in case of a communication break.
3
Speed ref safe Not applicable.
12.04 AI supervision
selection
Specifies the analog input limits to be supervised. See
parameter 12.03 AI supervision function.
0b0000
0b000...0b1111 Activation of analog input supervision. 1 = 1
12.11 AI1 actual value Shows value of analog input AI1 in mA or V (depending on
whether the input is set to current or voltage by a hardware
setting).
This parameter is read-only.
0.000
0.000…11.000 V Value of analog input AI1. 1000 = 1 unit
No. Name/Value Description Def/FbEq16
Bit Value
0 1 = Force AI1 to value of parameter 12.13 AI1 forced value.
1 1 = Force AI2 to value of parameter 12.23 AI2 forced value.
2…15 Reserved
Bit Name Description
0 AI1 < MIN 1 = Minimum limit supervision of AI1 active.
1 AI1 > MAX 1 = Maximum limit supervision of AI1 active.
2 AI2 < MIN 1 = Minimum limit supervision of AI2 active.
3 AI2 > MAX 1 = Maximum limit supervision of AI2 active.
4…15 Reserved
ACQ80 FW.book Page 84 Thursday, February 14, 2019 11:33 AM

Table of Contents

Other manuals for ABB ACQ80-04

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB ACQ80-04 and is the answer not in the manual?

ABB ACQ80-04 Specifications

General IconGeneral
BrandABB
ModelACQ80-04
CategoryDC Drives
LanguageEnglish

Related product manuals