Fieldbus control through a fieldbus adapter 259
The start sequence for the parameter example above is given below.
Control word:
• 477h (1143 decimal) –> READY TO SWITCH ON
• 47Fh (1151 decimal) –> OPERATING (Speed mode)
79.10 Operating mode 4 = Fieldbus A Selects fieldbus adapter A as the source
of the start and stop commands
1)
Read-only or automatically detected/set
2)
Example
Drive parameter Setting for ACS 560
drives
Description
ACQ80 FW.book Page 259 Thursday, February 14, 2019 11:33 AM