Fieldbus control through the embedded fieldbus interface (EFB) 233
15 Reserved
16 FB_LOCAL_CTL 1 Local mode for control from the fieldbus is requested.
Steal control from the active source.
0(no op)
17 FB_LOCAL_REF 1 Local mode for reference from the fieldbus is requested.
Steal reference from the active source.
0(no op)
18 Reserved for
RUN_DISABLE_1
Not yet implemented.
19 Reserved
20 Reserved
21 Reserved
22 USER_0 Writable control bits that can be combined with drive logic
for application-specific functionality.
23 USER_1
24 USER_2
25 USER_3
26…
31
Reserved
Bit Name Value State/Description
ACQ80 FW.book Page 233 Thursday, February 14, 2019 11:33 AM