118 Technical data
Losses, cooling data and noise
1)
The table shows the typical drive losses when it operates at 90% of the nominal output frequency and 100%
of the nominal output current. See IEC61800-9-2.
Terminal and lead-through data for the power cables
The maximum accepted cable size is 4 × (3 × 240) mm
2
or 4 × (3 × 500 AWG). Screw size
for connecting busbars to the drive module input and output busbars: M12, tightening
torque 50...75 N·m.
Drive modules without output cable connection terminals (+0H371)
and with a common mode filter (+E208)
It is possible to use the maximum cable size (4 × [3 × 240] mm
2
or 4 ×[(3 × 500 AWG]) only
with special cable lugs and additional insulation. For more information, contact your local
ABB representative.
Terminal data for the control cables
See page 84.
Drive type Frame size Air flow Heat dissipation
1)
Noise
m
3
/h ft
3
/min W dB(A)
ACS530-505A-4 R10 1200 707 6492 72
ACS530-585A-4 R10 1200 707 6840 72
ACS530-650A-4 R10 1200 707 8064 72
ACS530-725A-4 R11 1200 707 8108 72
ACS530-820A-4 R11 1200 707 9652 72
ACS530-880A-4 R11 1420 848 10887 71
3AXD00000586715