EasyManuals Logo
Home>ABB>Media Converter>DCS 600 MultiDrive

ABB DCS 600 MultiDrive Manual

ABB DCS 600 MultiDrive
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
II F 2-17
3ADW000072R0501_DCS600_System_description_e_e
2.6 Options
Line reactors
for armature (DCS 60x) and field
(DCF 60x) supply
When thyristor power converters operate, the line
voltage is short-circuited during commutation from
one thyristor to the next. This operation causes voltage
dips in the mains. For the connection of a power
converter system to the mains, a decision is made
between the following configurations:
With reference to the power converter:
The line reactors listed in table (2.6/1)
- have been allocated to the units nominal current
- are independent of converter's voltage classifica-
tion; at some converter types the same line choke
is used up to 690 V line voltage
- are based on a duty cycle
- can be used for DCS 600 as well as for DCF 600
converters
Connecting
point
Line
u
k LR
ca. 1%
Configuration A
When using the power converter, a
minimum of impedance is required to
ensure proper performance of the snub-
ber circuit. A line reactor can be used to
meet this minimum impedance require-
ment. The value must therefore not
drop below 1% u
k
(relative impedance
voltage). It should not exceed 10% u
k
, due to consider-
able voltage drops which would then occur.
Connecting
point
Line
L
Line
L
LR
Configuration B
If special requirements have to be met at
the connecting point, different criteria
must be applied for selecting a line
reactor. These requirements are often
defined as a voltage dip in percent of the
nominal supply voltage.
The combined impedance of Z
Line
and
Z
LR
constitute the total series imped-
ance of the installation. The ratio be-
tween the line impedance and the line reactor imped-
ance determines the voltage dip at the connecting
point. In such cases line chokes with an impedance
around 4% are often used.
Configuration C
If an isolation transformer is used, it is
possible to comply with certain con-
necting conditions per Configuration
B without using an additional line reac-
tor. The condition described in Con-
figuration A will then likewise be satis-
fied, since the u
k
is >1 %.
Connecting
point
Line
Configuration C1
If 2 or more converters should be sup-
plied by one transformer the final con-
figuration depends on the number of
drives in use and their power capability.
Configuration A or B has to be used
which are based on commutation
chokes, if the drive system consists of
C1, C2 or A5 converters. In case only
two converters type A6 / A7 (A6 + A6,
A6 + A7, A7 + A7) are involved no
commutation chokes are necessary because the design
of these converters is adapted to that wiring.
Line
Connecting
point
L
LR
L
LR
You will find further information in publication:
Technical Guide chapter: Line reactors

Other manuals for ABB DCS 600 MultiDrive

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB DCS 600 MultiDrive and is the answer not in the manual?

ABB DCS 600 MultiDrive Specifications

General IconGeneral
BrandABB
ModelDCS 600 MultiDrive
CategoryMedia Converter
LanguageEnglish

Related product manuals