Table 2–4 12 VDC Battery Power Supply System Maximum Cable Lengths
Model
/Option
Voltage
Units
10 AWG
1
12 AWG 14 AWG 16 AWG
6 mm^2
1
4 mm^2
1
2.5 mm^2 1.5 mm^2
12 VDC NGC w/o
Feed-through heater
12.00
(ft) 78.28 49.44 30.97 19.43 90.03 60.17 37.42 22.92
(m) 23.86 15.07 9.44 5.92 27.44 18.34 11.41 6.99
12 VDC NGC with
Feed-through heater
12.00
(ft) 38.74 24.47 15.32 9.62 44.55 29.78 18.52 11.34
(m) 11.81 7.46 4.67 2.93 13.58 9.08 5.64 3.46
Table 2–5 AC Power Supply System Maximum Cable Lengths
(No External Devices connected to NGC, AC Power Supply Only)
/Option
PS Voltage (V)
Units
10 AWG
1
12 AWG 14 AWG 16 AWG
6 mm^2
1
4 mm^2
1
2.5 mm^2 1.5 mm^2
12 VDC NGC w/o
Feed-through heater
14.50
(ft) 469.67 296.64 185.81 116.61 540.20 361.03 224.55 137.54
(m) 143.16 90.41 56.63 35.54 164.65 110.04 68.44 41.92
12 VDC NGC with
Feed-through heater
14.50
(ft) 232.43 146.80 91.95 57.71 267.33 178.66 111.12 68.06
(m) 70.84 44.74 28.03 17.59 81.48 54.46 33.87 20.75
24 VDC NGC w/o
Feed-through heater
25.00
(ft) 809.52 511.27 320.25 200.98 931.07 622.26 387.02 237.06
(m) 246.74 155.84 97.61 61.26 283.79 189.67 117.96 72.26
24 VDC NGC with
Feed-through heater
25.00
(ft) 336.97 212.83 133.31 83.66 387.57 259.03 161.10 98.68
(m) 102.71 64.87 40.63 25.50 118.13 78.95 49.10 30.08
1
This wire size may require splicing in 12AWG or 2.5mm^2 or smaller wires at each end of the cable to be able to fit screw terminals.