EasyManuals Logo
Home>ABB>Controller>PST Series

ABB PST Series User Manual

ABB PST Series
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #131 background image
131
1SFC132003M0201
)XQFWLRQV
&KDSWHU
 8QGHUORDGSURWHFWLRQWLPH
3DWKLQPHQX
0HQX6(77,1*6)XQFWLRQDO6HWWLQJV
3URWHFWLRQV8QGHUORDG8QGHUO7LPH
This parameter makes it possible to set the delay time
from detection until the protection is activated. It is active
only if underload protection is selected.
 8QGHUORDGSURWHFWLRQW\SHRI
RSHUDWLRQ
3DWKLQPHQX
0HQX6(77,1*6)XQFWLRQDO6HWWLQJV
3URWHFWLRQV8QGHUORDG8QGHUO2S
This parameter makes it possible to select between three
different actions of the softstarter when the protection is
activated. It is active only if the underload protection is
selected.
3DUDPHWHU
WH[W
'HIDXOWYDOXH 6HWWLQJUDQJH 'HVFULSWLRQ
Underl
Time
10 s 1...30 s Trip time for
Underload pro-
tection
Stop–M The motor stops and a manual reset is
required before restart.
Stop–A The motor stops and an automatic reset is
performed when the fault disappears.
Ind The motor continues to run but a fault indi-
cation is given.
3DUDPHWHU
WH[W
'HIDXOWYDOXH 6HWWLQJUDQJH 'HVFULSWLRQ
Underl Op Stop–M Stop–M, Stop–A,
Ind
Type of opera-
tion for Under-
load protection

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB PST Series and is the answer not in the manual?

ABB PST Series Specifications

General IconGeneral
BrandABB
ModelPST Series
CategoryController
LanguageEnglish

Related product manuals