164 1SFC132003M0201
7URXEOHVKRRWLQJ
&KDSWHU
 3URWHFWLRQLQGLFDWLRQ
6WDWXV 3RVVLEOHFDXVH 6ROXWLRQ
0RWRURYHUORDGSURWHFWLRQ The motor has been exposed to
an overload condition because
the current over a certain time is
too high.
(The load on the motor shaft is
too high)
,Q/LQH
$WVWDUW
Check and correct the reason for the
overload. Check that current limit level is
not set too low.
Check that the ramp time for start is not
too long.
Check that correct overload class is
used.
Check that parameter Setting Ie is cor-
rect.
&RQWLQXRXVUXQ
Check and correct the reason for the
overload.
,QVLGH'HOWD
$WVWDUW
Check and correct the reason for the
overload.
Check that current limit level is not set
too low.
Check that the ramp time for start is not
too long.
Check that correct overload class is
used.
Check that parameter Setting Ie is set to
58% ( ) of the rated motor current.
&RQWLQXRXVUXQ
Check and correct the reason for the
overload
Power on ProtectionFault
2TQV/QVQT1.
4GUGV $CEM
13e