EasyManuals Logo
Home>ABB>Controller>PST Series

ABB PST Series User Manual

ABB PST Series
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #134 background image
134 1SFC132003M0201
)XQFWLRQV
&KDSWHU
 +LJKFXUUHQWSURWHFWLRQW\SHRI
RSHUDWLRQ
3DWKLQPHQX
0HQX6(77,1*6)XQFWLRQDO6HWWLQJV
3URWHFWLRQV+LJK,+LJK,2S
This parameter makes it possible to select between three
different actions of the softstarter when the protection is
activated. It is active only if the high current protection is
selected.
 3KDVHUHYHUVDOSURWHFWLRQ
3DWKLQPHQX
0HQX6(77,1*6)XQFWLRQDO6HWWLQJV
3URWHFWLRQV3KDVH5HY
The softstarter accepts any phase sequence but if this
protection is selected, the phase sequence must be L1,
L2, L3 or else the protection is activated.
Stop–M The motor stops and a manual reset is
required before restart.
Stop–A The motor stops and an automatic reset is
performed when the fault disappears.
Ind The motor continues to run but a fault indi-
cation is given.
3DUDPHWHU
WH[W
'HIDXOWYDOXH 6HWWLQJUDQJH 'HVFULSWLRQ
High I Op Stop–M Stop–M, Stop–A,
Ind
Type of opera-
tion for high cur-
rent protection
3DUDPHWHU
WH[W
'HIDXOWYDOXH 6HWWLQJUDQJH 'HVFULSWLRQ
Phase Rev No Yes, No Phase reversal
protection

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB PST Series and is the answer not in the manual?

ABB PST Series Specifications

General IconGeneral
BrandABB
ModelPST Series
CategoryController
LanguageEnglish

Related product manuals