137
1SFC132003M0201
)XQFWLRQV
&KDSWHU
%\3DVVIDXOWW\SHRIRSHUDWLRQ
3DWKLQPHQX
0HQX6(77,1*6)XQFWLRQDO6HWWLQJV
)DXOWV%3)DXOW2S
This parameter makes it possible to select between three
different actions of the softstarter when the protection is
activated. It is active only if the by-pass monitor protection
is selected.
+LJKFXUUHQWZDUQLQJ
3DWKLQPHQX
0HQX6(77,1*6)XQFWLRQDO6HWWLQJV
:DUQLQJV:DUQ, +LJK
If the function is selected, a warning signal will be given
provided that the current during full voltage is higher than
the set value. The measurement starts 30 seconds after
IXOOYROWDJH is reached.
Stop–M The motor stops and a manual reset is
required before restart.
Stop–A The motor stops and an automatic reset is
performed when the fault disappears
3DUDPHWHU
WH[W
'HIDXOWYDOXH 6HWWLQJUDQJH 'HVFULSWLRQ
BP Fault
Op
Stop–M Stop–M, Stop–A Type of opera-
tion for Bypass
fault
3DUDPHWHU
WH[W
'HIDXOWYDOXH 6HWWLQJUDQJH 'HVFULSWLRQ
Warn
I=High
No Yes, No High current
warning