162 1SFC132003M0201
7URXEOHVKRRWLQJ
&KDSWHU
%\3DVVIDXOW The by-pass contactor is not
closing or opening properly.
:LWKRXWE\SDVV
• Check that the parameter ([W%\3DVV is
set to No.
:LWKE\SDVV
• Check why the contactor is not opening /
closing and make necessary actions.
• Check that the parameter ([W%\3DVV is
set to Yes
+HDWVLQNRYHUWHPSHUDWXUH
IDXOW
Temperature too high on the
heat sink. If the fault remains
after reset, the heat sink temper-
ature is too warm.
• Check that the fans are working in a
proper way.
• Check that cooling airways are free from
dirt and dust.
• Check that the ambient temperature is
not too high.
.LFNFXUUHQWIDXOW Parameter 6HWWLQJ,
H
is set too
low.
,Q/LQHFRQQHFWHG
• Set the value according to the rated
motor current.
,QVLGH'HOWD
• Set the value according to 58% ( )
of the rated motor current.
6KRUWHGWK\ULVWRUIDXOW One or several SCRs are
shorted.
• Check and replace. Contact your ABB
sales office for replacement kit.
1RQFRQGXFWLQJWK\ULVWRUIDXOW One or several SCRs are not
conducting.
• Check and replace. Contact your ABB
sales office for replacement kit.
6WDWXV 3RVVLEOHFDXVH 6ROXWLRQ
Power on ProtectionFault
(CWNV$[2CUU
4GUGV $CEM
Power on ProtectionFault
(CWNV*56GOR
4GUGV $CEM
Power on ProtectionFault
(CWNV-KEM%WT
4GUGV $CEM
13e
Power on ProtectionFault
(CWNV5%5%4
4GUGV $CEM
Power on ProtectionFault
(CWNV1RGP5%4
4GUGV $CEM