Section 2 Modbus data mappings
2.1 Overview
This document describes the Modbus data points and structures available in the
protection relay. The point lists describe a superset of all data available through the
standard configuration/s including the optional functionalities.
The majority of the Modbus data points are valid for all standard configurations. Some
data points are standard configuration-dependent or optional application-dependent
and thus not available in each protection relay. The unavailable, that means, unused,
data points always return value 0 when they are read. The configuration-dependent
and optional data do not overlap.
2.2 Supported functions
2.2.1 Supported functions in RET615
Table 2: Supported functions
Function
IEC 61850 A B C D E F G H
TE01 TE02 TE03 TE04 TE05 TE06 TE07 TE08
Protection
Three-phase non-directional overcurrent
protection, low stage
PHLPTOC1
1
HV
1
HV
1
HV
1
HV
1
HV
1
HV
1
HV
1
HV
PHLPTOC2
1
LV
1
LV
1
LV
1
LV
1
LV
1
LV
1
LV
1
LV
Three-phase non-directional overcurrent
protection, high stage
PHHPTOC1
1
HV
1
HV
1
HV
1
HV
1
HV
1
HV
1
HV
1
HV
PHHPTOC2
1
LV
1
LV
1
LV
1
LV
1
LV
1
LV
1
LV
1
LV
Three-phase non-directional overcurrent
protection, instantaneous stage
PHIPTOC1
1
HV
1
HV
1
HV
1
HV
1
HV
1
HV
1
HV
1
HV
PHIPTOC2
1
LV
1
LV
1
LV
1
LV
1
LV
1
LV
1
LV
1
LV
Non-directional earth-fault protection, low
stage
EFLPTOC1
1
HV
1
HV 1)
1
HV
1
HV 1)
EFLPTOC2
1
LV
1
LV 2)
1
LV
1
LV 2)
Non-directional earth-fault protection, high
stage
EFHPTOC1
1
HV
1
HV 1)
1
HV
1
HV 1)
EFHPTOC2
1
LV
1
LV 2)
1
LV
1
LV 2)
Negative-sequence overcurrent protection NSPTOC1
1
HV
1
HV
1
HV
1
HV
1
HV
1
HV
1
HV
1
HV
NSPTOC2
1
LV
1
LV
1
LV
1
LV
1
LV
1
LV
1
LV
1
LV
Residual overvoltage protection ROVPTOV
2
HV
2
HV
2
HV
2
HV
Three-phase undervoltage protection PHPTUV
2
HV
2
HV
2
HV
2
HV
Three-phase overvoltage protection PHPTOV
2
HV
2
HV
2
HV
2
HV
Three-phase thermal overload protection,
two time constants
T2PTTR
1
HV
1
HV
1
HV
1
HV
1
HV
1
HV
1
HV
1
HV
Stabilized and instantaneous differential
protection for two-winding transformers
TR2PTDF 1 1 1 1 1 1 1 1
Numerically stabilized low-impedance
restricted earth-fault protection
LREFPNDF
1
HV
1
LV
1
HV
1
LV
Table continues on next page
1MRS756878 H Section 2
Modbus data mappings
RET615 15
Point List Manual

Table of Contents

Other manuals for ABB RET615

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RET615 and is the answer not in the manual?

ABB RET615 Specifications

General IconGeneral
Rated Frequency50/60 Hz
WeightApprox. 2.5 kg
TypeProtection Relay
Communication ProtocolsIEC 61850, Modbus, DNP3
Protection FunctionsOvercurrent, Earth fault, Thermal overload, Frequency
Input Voltage24-250 V DC

Related product manuals