RegA Type Scale IEC 61850 name SA name Description Values
2044 u16 - Minute - second
2045 u16 - Milliseconds
2046 u16 - Time quality
2047 u16 1000 .MaxAmpsC.mag Max demand IL3 Max. phsC demand
0.00...40.0
[xIn]
Update time stamp see doc.
2048 u16 - Year - month
2049 u16 - Day - hour
2050 u16 - Minute - second
2051 u16 - Milliseconds
2052 u16 - Time quality
2.4.1.32 LD0.CMMXU2 Three-phase current measurement (2)
Table 135: LD0.CMMXU2 Three-phase current measurement (2)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.CMMXU2 Phase current (2)
152 u16 1000 .A.phsA.instCVal.mag I_INST_A Phs A amplitude
0.00...40.0
[xIn]
153 u16 1000 .A.phsB.instCVal.mag I_INST_B Phs B amplitude
0.00...40.0
[xIn]
154 u16 1000 .A.phsC.instCVal.mag I_INST_C Phs C amplitude
0.00...40.0
[xIn]
2.4.1.33 LD0.CSMSQI1 Sequence current measurement (1)
Table 136: LD0.CSMSQI1 Sequence current measurement (1)
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.CSMSQI1 Sequence of currents
142 u16 1000 .SeqA.c1.instCVal.mag I1_INST Positive amplitude
0.00...40.0
[xIn]
143 u16 1000 .SeqA.c2.instCVal.mag I2_INST Negative amplitude
0.00...40.0
[xIn]
144 u16 1000 .SeqA.c2.instCVal.mag I3_INST Zero amplitude
0.00...40.0
[xIn]
Section 2 1MRS756878 H
Modbus data mappings
74 RET615
Point List Manual

Table of Contents

Other manuals for ABB RET615

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RET615 and is the answer not in the manual?

ABB RET615 Specifications

General IconGeneral
BrandABB
ModelRET615
CategoryProtection Device
LanguageEnglish

Related product manuals