2.3.1.64 LD0.TRPPTRC1 Master trip (1)
Table 67: LD0.TRPPTRC1 Master trip (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.TRPPTRC1
2740 171.04 .Op.general - Op. input signal 1=Operate
2741 171.05 .mcd
2742 171.06 .Tr.general - Trip output signal 1=Trip
2743 171.07 .mcd
2.3.1.65 LD0.TRPPTRC2 Master trip (2)
Table 68: LD0.TRPPTRC2 Master trip (2)
BitA RegA IEC 61850 name SA name Description Values
LD0.TRPPTRC2
2744 171.08 .Op.general - Op. input signal 1=Operate
2745 171.09 .mcd
2746 171.10 .Tr.general - Trip output signal 1=Trip
2747 171.11 .mcd
2.3.1.66 LD0.VMMXU1 Three-phase voltage measurement (1)
Table 69: LD0.VMMXU1 Three-phase voltage measurement (1)
BitA
RegA IEC 61850 name SA name Description Values
LD0.VMMXU1
3040 190.00 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm
3041 190.01 .mcd
3042 190.02 .HiWrn.stVal HIGH_WARN High warning 1=Warning
3043 190.03 .mcd
3044 190.04 .LoWrn.stVal LOW_WARN Low warning 1=Warning
3045 190.05 .mcd
3046 190.06 .LoAlm.stVal LOW_ALARM Low alarm 1=Alarm
3047 190.07 .mcd
1MRS756878 H Section 2
Modbus data mappings
RET615 41
Point List Manual

Table of Contents

Other manuals for ABB RET615