2.5.7 LD0.SPCGAPC1 Generic control point (16 pcs) (1)
The binary outputs can be configured either as pulse- or persistent-type outputs. Pulse-
type outputs are triggered with the write value "1". Persistent-type outputs can be
written with both values "1" and "0". The setting mode "toggled" for local operation
corresponds to "persistent" for remote operation.
Table 171: LD0.SPCGAPC1 Generic control point (16 pcs) (1)
0xA CS IEC 61850 name SA name Description Values
LD0.SPCGAPC1
2112 5.00 .SPCS01.ctlVal Output 1 control 0/1=Off/On
2113 5.01 .SPCS02.ctlVal Output 2 control 0/1=Off/On
2114 5.02 .SPCS03.ctlVal Output 3 control 0/1=Off/On
2115 5.03 .SPCS04.ctlVal Output 4 control 0/1=Off/On
2116 5.04 .SPCS05.ctlVal Output 5 control 0/1=Off/On
2117 5.05 .SPCS06.ctlVal Output 6 control 0/1=Off/On
2118 5.06 .SPCS07.ctlVal Output 7 control 0/1=Off/On
2119 5.07 .SPCS08.ctlVal Output 8 control 0/1=Off/On
2120 5.08 .SPCS09.ctlVal Output 9 control 0/1=Off/On
2121 5.09 .SPCS10.ctlVal Output 10 control 0/1=Off/On
2122 5.10 .SPCS11.ctlVal Output 11 control 0/1=Off/On
2123 5.11 .SPCS12.ctlVal Output 12 control 0/1=Off/On
2124 5.12 .SPCS13.ctlVal Output 13 control 0/1=Off/On
2125 5.13 .SPCS14.ctlVal Output 14 control 0/1=Off/On
2126 5.14 .SPCS15.ctlVal Output 15 control 0/1=Off/On
2127 5.15 .SPCS16.ctlVal Output 16 control 0/1=Off/On
2.5.8 LD0.SPCGAPC2 Generic control point (16 pcs) (2)
The binary outputs can be configured either as pulse- or persistent-type outputs. Pulse-
type outputs are triggered with the write value "1". Persistent-type outputs can be
written with both values "1" and "0". The setting mode "toggled" for local operation
corresponds to "persistent" for remote operation.
Table 172: LD0.SPCGAPC2 Generic control point (16 pcs) (2)
0xA
CS IEC 61850 name SA name Description Values
LD0.SPCGAPC2
2128 6.00 .SPCS01.ctlVal Output 1 control 0/1=Off/On
2129 6.01 .SPCS02.ctlVal Output 2 control 0/1=Off/On
2130 6.02 .SPCS03.ctlVal Output 3 control 0/1=Off/On
2131 6.03 .SPCS04.ctlVal Output 4 control 0/1=Off/On
2132 6.04 .SPCS05.ctlVal Output 5 control 0/1=Off/On
Table continues on next page
1MRS756878 H Section 2
Modbus data mappings
RET615 87