BitA RegA IEC 61850 name SA name Description Values
3474 217.02 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
3475 217.03 .Pos.stSeld - Control selected 1=Selected
CTRL.DCCILO1
3476 217.04 .EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
3477 217.05 .EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
CTRL.DCXSWI1
3478 217.06 .BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
3479 217.07 .mcd
3480 217.08 .BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
3481 217.09 .mcd
CTRL.DCCILO1
3482 217.10 .ItlByps.stVal ITL_BYPASS Interlock bypass 1=Bypass
3483 217.11 .mcd
2.3.1.10 CTRL.DCXSWI2 Disconnector control (2)
Table 13: CTRL.DCXSWI2 Disconnector control (2)
BitA
RegA IEC 61850 name SA name Description Values
CTRL.DCXSWI2 POSITION
3484 217.12 .Pos.stVal.Close - Close bit 1=Close
3485 217.13 .Pos.stVal.Open - Open bit 1=Open
3486 217.14 .Pos.stVal.Fault - Fault bit 1=Pos(00/11)
3487 217.15 .Pos.stSeld - Control selected 1=Selected
CTRL.DCCILO2
3488 218.00 .EnaOpn.stVal ENA_OPEN Open enabled 1=Enabled
3489 218.01 .EnaCls.stVal ENA_CLOSE Close enabled 1=Enabled
CTRL.DCXSWI2
3490 218.02 .BlkOpn.stVal BLK_OPEN Open blocked 1=Blocked
3491 218.03 .mcd
3492 218.04 .BlkCls.stVal BLK_CLOSE Close blocked 1=Blocked
3493 218.05 .mcd
CTRL.DCCILO2
3494 218.06 .ItlByps.stVal ITL_BYPASS Interlock bypass 1=Bypass
3495 218.07 .mcd
Section 2 1MRS756878 H
Modbus data mappings
20 RET615