little meaning, since it is always possible to redefine the settings completely for the
user-definable register.
2.4.2.1 CTRL.LLN0 Local, Remote, Station, Off and Combinations
Table 155: CTRL.LLN0 Local, Remote, Station, Off and Combinations
RegA Type Scale IEC 61850 name SA name Description Values
CTRL.LLN0
u16 1 .LocKeyHMI.stVal
0=Off; 1=Loc; 2=Rem; 3=Stat;
4=L+R; 5=L+S; 6=L+S+R; 7=S
+R
0…7
2.4.2.2 LD0.FMMXU1 Frequency measurement (1)
Table 156: LD0.FMMXU1 Frequency measurement (1)
RegA Type Scale IEC 61850 name SA name Description Values
LD0.FMMXU1
u16 100 .Hz.mag F_DB Frequency
35.00...75.00
[Hz]
2.4.2.3 LD0.LLN0/LPHD1/LDEV1 System values
Table 157: LD0.LLN0/LPHD1/LDEV1 System values
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.LLN0
u16 1 .ParChgCnt.stVal Num. of setting changes 0…65535
2.4.2.4 LD0.MDSOPT1 Runtime counter for machines and devices (1)
Table 158: LD0.MDSOPT1 Runtime counter for machines and devices (1)
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.MDSOPT1
u16 1 .OpTmh.stVal OPR_TIME Total operation hours 0…299999
2.4.2.5 LD0.MVI4GAPC1 Integer value move (1)
Table 159: LD0.MVI4GAPC1 Integer value move (1)
RegA
Type Scale IEC 61850 name SA name Description Values
LD0.MVI4GAPC1
i32 1 .ISCS01.stVal OUT1 - Integer value 1 (high)
-/
+2147483647
- Low word
Table continues on next page
Section 2 1MRS756878 H
Modbus data mappings
82 RET615
Point List Manual