Main menu/Settings/General settings/Communication/Station communication/
MultiCommandSend/MULTICMDSND:x
Includes available instances of Multicommand send settings allowing the user to
adjust the maximum and minimum cycle time.
Multicommand receive
Main menu/Settings/General settings/Communication/Station communication/
MultiCommandReceive/MULTICMDRCV:x
Includes available instances of Multicommand receive settings allowing the user to
adjust the maximum and minimum cycle time, the pulse duration and mode of
operation. The mode of operation is either steady or pulsed.
Horizontal communication via GOOSE for interlocking
Main menu/Settings/General settings/Communication/Station communication/
ReceivingInterlInfo/GOOSEINTLKRCV:x
Includes available instances of GOOSEINTLKRCV for horizontal communication
via GOOSE. Each instance or set can be switched On or Off via the Operation On
and Off parameter.
9.2.2.5 Ethernet configuration
Main menu/Settings/General settings/Communication/Ethernet configuration/
Front port
The IP Address and IP mask for the ethernet port on the front panel of the IED are
set here. These are generally used when connecting a PC directly to the IED.
Remember that this is a static IP address and that the appropriate network settings
must also be made in the PC.
Main menu/Settings/General settings/Communication/Ethernet configuration/
Rear OEM-Port AB
The IP address, IP mask and Mode for the IEC 61850-8-1 communication using the
Optical Ethernet Module (OEM) at the rear of the IED are set here.
Main menu/Settings/General settings/Communication/Ethernet configuration/
Rear OEM-Port CD
The IP address (with different IP address when a second channel is used), IP mask
and Mode for the Optical Ethernet Module (OEM) at the rear of the IED are set
here. The CD port is used for IEC 61850-9-2LE communication.
Main menu/Settings/General settings/Communication/Ethernet configuration/
Rear OEM - Redundant PRP
Redundant station bus communication IEC61850-8-1 are set here.
Section 9 1MRK504114-UEN E
Read and change settings
46
Operator's manual

Table of Contents

Other manuals for ABB RET670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RET670 and is the answer not in the manual?

ABB RET670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
InputsAnalog and binary inputs
ApplicationProtection of power systems
Communication ProtocolsIEC 61850, DNP3, Modbus
Operating Temperature Range-25°C to +55°C
MountingRack mounted
Number of Binary InputsUp to 48
Number of Binary Outputs32
Protection FunctionsOvercurrent Protection
OutputsBinary outputs
EnclosureIP 54
TypeLine Differential Protection