Section 11 Test the IED
About this chapter
This chapter describes the tests that can be performed in the test section of the HMI.
11.1 Overview
The test part of the tree view in the HMI has a number of submenus for test and
viewing activities. When the IED Testmode is set to On, the functions are
deactivated and no signals are transmitted during testing. Under Function test
modes individual functions can be activated. The LED test is also activated here.
The submenus for binary inputs and outputs as well as the submenu titled Function
status are used to view data generated by the system. These categories of data are
outlined below.
1. Binary output values has two submenus. These are Binary output modules
(BOM) and SMT binary outputs. Under these the status of binary outputs and
SMT outputs is displayed.
2. Binary input values has two submenus. These are Binary input modules (BIM)
and SMT binary inputs. These screens show the state of all the inputs on the
Binary input modules (BIM). These are represented as digits but may also be a
number if the input is being used to receive pulses for power measurement.
3. Differential Protection displays a choice of differential functions available to
the operator. Function related measurements can be viewed by navigating to
the screen for each individual function.
4. Distance protection displays a choice of functions available to the operator.
Function related measurements can be viewed by navigating to the screen for
each individual function.
5. Current protection displays a choice of functions. To view data related to these
functions it is necessary to choose one from the list and navigate to the screen
for the function in question.
6. Voltage protection displays a choice of functions available to the operator.
Function related measurements can be viewed by navigating to the screen for
each of the four functions available. Data shown here is mainly trip and start
related.
7. Frequency protection includes measurements from frequency functions.
Measurements show trip, start and similar data.
8. Multipurpose protection includes measurements showing data regarding trip
signals, start signals, current and voltage values.
9. Secondary system supervision displays a choice of functions, Current circuit
supervision and Fuse failure. Current circuit measurements include fail and
alarm signals, and fuse failure measurements consist of start data.
1MRK504114-UEN E Section 11
Test the IED
73
Operator's manual

Table of Contents

Other manuals for ABB RET670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RET670 and is the answer not in the manual?

ABB RET670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
InputsAnalog and binary inputs
ApplicationProtection of power systems
Communication ProtocolsIEC 61850, DNP3, Modbus
Operating Temperature Range-25°C to +55°C
MountingRack mounted
Number of Binary InputsUp to 48
Number of Binary Outputs32
Protection FunctionsOvercurrent Protection
OutputsBinary outputs
EnclosureIP 54
TypeLine Differential Protection