Rockwell Automation Publication 1756-UM001M-EN-P - February 2012 145
I/O Modules Chapter 8
Other Devices that Can be Added While Online
• 1305-BAXXA drives
• 1336E-IMPACT™Drive-EN1 drive
• 1336F-PLUS™IIDrive-EN1drive
• 1336R-REGENBrake-EN1 brake
• 1336S-PLUSDriveLG-EN1 drive
• 1336S-PLUSDriveSM-EN1 drive
• 1336T-FORCE™DriveCNA-EN1 drive
• 1336T-FORCEDrivePLC-EN1 drive
• 1336T-FORCEDriveStd-EN1 drive
• 1397DigitalDCDrive-EN1 drive
• 150 SMC™ FLEX motor controller
• 150-SMC™DialogPlus-EN1 motor controller
• 1757-FFLDC ControlNet Foundation Fieldbus device
• 2364F RGU-EN1 bus supply
• 48MS-SN1PF1-M2 Multivision Sensor
• 5XRF RFID interface device
Online Additions - ControlNet Considerations
ControlNet considerations that must be made depend upon the ControlLogix
ControlNet modules you are using.
1756-CNB and 1756-CNBR Modules
When you add I/O to the ControlNet network via the 1756-CNB or
1756-CNBR modules while online, these considerations must be made:
• Digital I/O modules can be added as rack-optimized connections if the
parent module is already configured with rack-optimized connections.
• Digital I/O modules can also be added as direct connections.
• Analog I/O modules can be added only as direct connections.
• Disable the Change of State (COS) feature on digital input modules
because it can cause inputs to be sent more quickly than the RPI.
While you can add a new digital I/O module to an existing rack-optimized
connection, you cannot add rack-optimized connections while online.