Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 101
Programming and Parameters Chapter 3
R253 [Aux AutoSwap Tme]
Sets the total running time between automatic motor changes.
Values Default: 0.0 Hr
Min/Max: 0.0/999.9 Hr
Display: 0.1 Hr
IMPORTANT
Proper wiring and parameter configuration of Aux Motor Control functions are especially important when using AutoSwap. Improper wiring or
configuration could result in line power being applied to the drive outputs. Verify system operation before connecting auxiliary motor contactor outputs.
R254 [Aux AutoSwap Lvl]
Sets the maximum level allowable for an AutoSwap to occur. If the PID output is above this level, AutoSwap will be delayed until the PID output drops below this parameter setting.
Values Default: 50.0%
Min/Max: 0.0/100.0%
Display: 0.1%