Rockwell Automation Publication 22C-UM001J-EN-E - January 2017 79
Programming and Parameters Chapter 3
Communications Group
C101 [Language]
Selects the language displayed by the integral LCD display and remote communications option.
Options 1 “English” (Default)
2“Français”
3“Español”
4 “Italiano”
5“Deutsch”
6 “Reserved”
7“Português”
8 “Reserved”
9 “Reserved”
10 “Nederlands”
C102 [Comm Format] Related Parameter(s): d303...d306
Selects the protocol data bits (8 data bits only), parity (None, Even, Odd), and stop bits (1 or 2) used by the RS485 port on the drive.
Refer to Appendix D and Appendix E for details on using the drive communication features.
Options 0 “RTU 8-N-1” (Default)
1“RTU 8-E-1”
2 “RTU 8-O-1”
3 “RTU 8-N-2”
4“RTU 8-E-2”
5 “RTU 8-O-2”
6“MetaSys N2”
7 “P1 8-N-1” Floor Level Network (FLN)
8 “P1 8-E-1” Floor Level Network (FLN)
9 “P1 8-O-1” Floor Level Network (FLN)
IMPORTANT
Power to drive must be cycled before any changes will affect drive operation.
C103 [Comm Data Rate] Related Parameter(s): d303
Sets the serial port rate for the RS485 (DSI) port.
Options 0 “1200”
1 “2400”
2 “4800”
3 “9600” (Default)
4“19.2K”
5“38.4K”
IMPORTANT
Power to drive must be cycled before any changes will affect drive operation.