122 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Appendix A Supplemental Drive Information
Specifications
Drive Ratings
Catalog Number Output Ratings Input Ratings Branch Circuit Protection
kW (HP) Amps Voltage
Range
kVA Amps Fuses 140M Motor
Protectors
(1)(2)
Contactors Min.
Enclosure
Volumes
(3)
(in.
3
)
45 °C 50 °C
200...240V AC – 3-Phase Input, 0 - 230V 3-Phase Output
22C-B012N103 2.2 (3.0) 12 12 180-265 6.5 15.5 20 140M-F8E-C16 100-C23 5098
22C-B017N103 3.7 (5.0) 17.5 17.5 180-265 8.8 21 30 140M-F8E-C25 100-C37 5098
22C-B024N103 5.5 (7.5) 24 24 180-265 10.9 26.1 35 140M-F8E-C32 100-C37 5098
22C-B033N103 7.5 (10) 33 33 180-265 14.4 34.6 45 140M-F8E-C45 100-C45 5098
22C-B049A103 11 (15) 49 49 180-265 21.3 51 70 – 100-C60 –
22C-B065A103 15 (20) 65 65 180-265 28.3 68 90 – 100-C85 –
22C-B075A103 18.5 (25) 75 75 180-265 32.5 78 100 – 100-D95 –
22C-B090A103 22 (30) 90 81 180-265 38.3 92 125 – 100-D110 –
22C-B120A103 30 (40) 120 120 180-265 51.6 124 175 – 100-D180 –
22C-B145A103 37 (50) 145 130 180-265 62.4 150 200 – 100-D180 –
380...480V AC – 3-Phase Input, 0...460V 3-Phase Output
22C-D6P0N103 2.2 (3.0) 6 6 340-528 6.3 7.5 10 140M-D8E-C10 100-C09 5098
22C-D010N103 4.0 (5.0) 10.5 10.5 340-528 10.9 13 20 140M-D8E-C16 100-C16 5098
22C-D012N103 5.5 (7.5) 12 12 340-528 11.9 14.2 20 140M-D8E-C16 100-C23 5098
22C-D017N103 7.5 (10) 17 17 340-528 15.3 18.4 25 140M-D8E-C20 100-C23 5098
22C-D022N103 11 (15) 22 22 340-528 19.2 23 30 140M-F8E-C32 100-C30 5098
22C-D030N103 15 (20) 30 27 340-528 25.8 31 40 140M-F8E-C32 100-C37 5098
22C-D038A103 18.5 (25) 38 38 340-528 33.3 40 50 140M-F8E-C45 100-C60 9086
22C-D045A103 22 (30) 45.5 45.5 340-528 39.1 47 60 – 100-C60 –
22C-D060A103 30 (40) 60 54 340-528 53.3 64 80 – 100-C85 –
22C-D072A103 37 (50) 72 72 340-528 60.7 73 100 – 100-C85 –
22C-D088A103 45 (60) 88 88 340-528 74.9 90 125 – 100-D110 –
22C-D105A103 55 (75) 105 105 340-528 89 107 150 – 100-D140 –
22C-D142A103 75 (100) 142 128 340-528 124.8 150 200 – 100-D180 –
22C-D170A103 90 (125) 170 170 340-528 142 170 250 – 100-D250 –
22C-D208A103 110 (150) 208 208 340-528 167 200 250 – 100-D250 –
22C-D260A103 132 (200) 260 260 340-528 196 235 300 – 100-D300 –
22C-D310A103 160 (250) 310 290 340-528 242 290 400 – 100-D420 –
22C-D370A103 200 (300) 370 370 340-528 304 365 500 – 100-D420 –
22C-D460A103 250 (350) 460 410 340-528 387 465 600 – 100-D630 –
(1) The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M Motor Protection Circuit Breakers
Application Ratings.
(2) Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/347. Not UL
listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.
(3) When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated
enclosure with the minimum volume specified in this column. Application specific thermal considerations may require a larger enclosure.