80 Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Chapter 3 Programming and Parameters
C104 [Comm Node Addr] Related Parameter(s): d303
Sets the drive node address for the RS485 (DSI) port if using a network connection.
Values Default: 100
Min/Max: 1/247
Display: 1
IMPORTANT
Power to drive must be cycled before any changes will affect drive operation.
C105 [Comm Loss Action] Related Parameter(s): d303, P037, C106
Selects the drives response to a loss of the communication connection or excessive communication errors.
Options 0 “Fault” (Default) Drive will fault on an F81 Comm Loss and coast to stop.
1 “Coast Stop” Stops drive via coast to stop.
2 “Stop” Stops drive via P037
[Stop Mode] setting.
3 “Continu Last” Drive continues operating at communication commanded speed saved in RAM.
4 “Run Preset 0” Drive will run at preset speed.
5“Kypd Inc/Dec Drive will run at keypad (digital pot) speed.
C106 [Comm Loss Time] Related Parameter(s): d303, C105
Sets the time that the drive will remain in communication loss before implementing the option selected in C105 [Comm Loss Action].
Values Default: 5.0 Secs
Min/Max: 0.1/60.0 Secs
Display: 0.1 Secs
C107 [Comm Write Mode]
Determines whether parameter changes made over communication port are saved and stored in Non-Volatile Storage (NVS) or RAM only. If they are stored in RAM, the values will be
lost at power-down.
Options 0“Save (Default)
1“RAM Only
ATTENTION: Risk of equipment damage exists. If a controller is programmed to write parameter data to Non-Volatile Storage (NVS) frequently, the NVS will
quickly exceed its life cycle and cause the drive to malfunction. Do not create a program that frequently uses configurable outputs to write parameter data to
NVS unless C107 [Comm Write Mode] is set to option 1.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley 22C-D038A103 and is the answer not in the manual?

Allen-Bradley 22C-D038A103 Specifications

General IconGeneral
BrandAllen-Bradley
Model22C-D038A103
CategoryController
LanguageEnglish

Related product manuals