Table 4.3 DF1 Half-Duplex Configuration Parameters
Parameter Options
Baud Rate 300, 600, 1200, 2400, 4800, 9600, 19.2K, 38.4K
Parity none, even
Source ID (Node Address) 0 to 254 decimal
Control Line no handshaking, handshaking
Error Detection CRC, BCC
EOT Suppression enabled, disabled
When EOT Suppression is enabled, the slave does not respond when polled if no message is queued. This
saves modem transmission power and time when there is no message to transmit.
Duplicate Packet (Message)
Detect
enabled, disabled
Detects and eliminates duplicate responses to a message. Duplicate packets may be sent under noisy
communication conditions if the sender’s Message Retries are not set to 0.
Poll Timeout (x20 ms) 0 to 65535 (can be set in 20 ms increments)
Poll Timeout only applies when a slave device initiates a MSG instruction. It is the amount of time that the
slave device waits for a poll from the master device. If the slave device does not receive a poll within the
Poll Timeout, a MSG instruction error is generated, and the ladder program needs to requeue the MSG
instruction. If you are using a MSG instruction, it is recommended that a Poll Timeout value of zero not be
used. Poll Timeout is disabled when set to zero.
RTS Off Delay (x20 ms) 0 to 65535 (can be set in 20 ms increments)
Specifies the delay time between when the last serial character is sent to the modem and when RTS is
deactivated. Gives the modem extra time to transmit the last character of a packet.
RTS Send Delay (x20 ms) 0 to 65535 (can be set in 20 ms increments)
Specifies the time delay between setting RTS until checking for the CTS response. For use with modems
that are not ready to respond with CTS immediately upon receipt of RTS.
Message Retries 0 to 255
Specifies the number of times a slave device attempts to resend a message packet when it does not
receive an ACK from the master device. For use in noisy environments where message packets may
become corrupted in transmission.
Pre Transmit Delay
(x1 ms)
0 to 65535 (can be set in 1 ms increments)
When the Control Line is set to
no handshaking
, this is the delay time before transmission.
Required for 1761-NET-AIC physical Half-Duplex networks. The 1761-NET-AIC needs delay time to
change from transmit to receive mode.
When the Control Line is set to
DF1 Half-Duplex Modem
, this is the minimum time delay between
receiving the last character of a packet and the RTS assertion.

Table of Contents

Other manuals for Allen-Bradley micrologix 1500

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley micrologix 1500 and is the answer not in the manual?

Allen-Bradley micrologix 1500 Specifications

General IconGeneral
BrandAllen-Bradley
Modelmicrologix 1500
CategoryController
LanguageEnglish

Related product manuals