4-2 Troubleshooting
Fault Indication
Manually Clearing Faults
Automatically Clearing Faults
Auto Restart (Reset/Run)
The Auto Restart feature provides the ability for the drive to
automatically perform a fault reset followed by a start attempt without
user or application intervention. This allows remote or “unattended”
operation. Only certain faults are allowed to be reset. Certain faults
(Type 2) that indicate possible drive component malfunction are not
resettable. Fault types are listed in Table 4.A
. Refer to Table 4.B for fault
descriptions.
Caution should be used when enabling this feature, since the drive will
attempt to issue its own start command based on user selected
programming.
Condition Display
Drive is indicating a fault.
The integral LED display provides visual
notification of a fault condition by displaying the
following.
Flashing fault number
Flashing fault indicator
Press the Up Arrow key to regain control of the
display.
Step Key(s)
1. Address the condition that caused the fault.
The cause must be corrected before the fault can be cleared.
See Tabl e 4. B
.
2. After corrective action has been taken, clear the fault by one of these
methods.
Press and hold the Up Arrow key for three seconds.
Cycle drive power.
Set A100
[Fault Clear] to “1” or “2”.
Cycle digital input if A051
-A054 [Digital Inx Sel] is set to option 7
“Clear Fault”.
Option / Step
Clear a Type 1 fault and restart the drive.
1. Set A092
[Auto Rstrt Tries] to a value other than “0”.
2. Set A093
[Auto Rstrt Delay] to a value other than “0”.
Clear an OverVoltage, UnderVoltage or Heatsink OvrTmp fault
without restarting the drive.
1. Set A092
[Auto Rstrt Tries] to a value other than “0”.
2. Set A093
[Auto Rstrt Delay] to “0”.
RUN
REV
FAULT

Table of Contents

Other manuals for Allen-Bradley PowerFlex 40P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 40P and is the answer not in the manual?

Allen-Bradley PowerFlex 40P Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 40P
CategoryController
LanguageEnglish

Related product manuals