3-44 Programming and Parameters
Advanced Program Group (continued)
A140 [Stp Logic 0]
A141 [Stp Logic 1]
A142 [Stp Logic 2]
A143 [Stp Logic 3]
A144 [Stp Logic 4]
A145 [Stp Logic 5]
A146 [Stp Logic 6]
A147 [Stp Logic 7]
Related Parameter(s): P038, P039, P040, A051-A054,
A055
, A058, A061, A067, A068, A070-A077, A150-A157,
E248
Values Default: 00F1
Min/Max: 0001/FAFF
Display: 4 Digits
For detailed information on applying Step Logic and Position StepLogic refer to Appendix
E and
Appendix
F.
Parameters A140-A147 are only active if P038
[Speed Reference] is set to 6 “Stp Logic” or 9
“Positioning”.
These parameters can be used to create a custom profile of frequency commands. Each “step” can
be based on time, status of a Logic input or a combination of time and the status of a Logic input.
Digits 0-3 for each [Stp Logic x] parameter must be programmed according to the desired profile.
A Logic input is established by setting a digital input, parameters A051
- A054 [Digital Inx Sel], to 23
“Logic In1” and/or 24 “Logic In2” or by using Bits 6 and 7 of E248
[Enh Control Word].
A time interval between steps can be programmed using parameters A150
- A157 [Stp Logic Time x].
See the table below for related parameters.
The speed for any step is programmed using parameters A070
- A077 [Preset Freq x].
The position for any step is programmed using parameters E230
- E245 [Step Units x].
Stop drive before changing this parameter.
Step StepLogic Parameter
Related Preset Frequency Parameter
(Can be activated independent of
StepLogic Parameters)
Related StepLogic Time Parameter
(Active when A140-A147 Digit 0 or 1
are set to 1, b, C, d or E)
0 A140 [Stp Logic 0] A070 [Preset Freq 0] A150 [Stp Logic Time 0]
1 A141 [Stp Logic 1] A071 [Preset Freq 1] A151 [Stp Logic Time 1]
2 A142 [Stp Logic 2] A072 [Preset Freq 2] A152 [Stp Logic Time 2]
3 A143 [Stp Logic 3] A073 [Preset Freq 3] A153 [Stp Logic Time 3]
4 A144 [Stp Logic 4] A074 [Preset Freq 4] A154 [Stp Logic Time 4]
5 A145 [Stp Logic 5] A075 [Preset Freq 5] A155 [Stp Logic Time 5]
6 A146 [Stp Logic 6] A076 [Preset Freq 6] A156 [Stp Logic Time 6]
7 A147 [Stp Logic 7] A077 [Preset Freq 7] A157 [Stp Logic Time 7]
Step StepLogic Position Parameters
0 E230 [Step Units 0] & E231 [Step Units F 0]
1 E232 [Step Units 1] & E233 [Step Units F 1]
2 E234 [Step Units 2] & E235 [Step Units F 2]
3 E236 [Step Units 3] & E237 [Step Units F 3]
4 E238 [Step Units 4] & E239 [Step Units F 4]
5 E240 [Step Units 5] & E241 [Step Units F 5]
6 E242 [Step Units 6] & E243 [Step Units F 6]
7 E244 [Step Units 7] & E245 [Step Units F 7]