Programming and Parameters 3-23
Advanced Program Group (continued)
A066 [Analog Out High] Related Parameter(s): A065
Scales the Maximum Output Value for the A065 [Analog Out Sel] source setting.
Examples:
Values Default: 100%
Min/Max: 0/800%
Display: 1%
A066 Setting A065 Setting A065 Max. Output Value
50% 1 “OutCurr 0-10” 5V for 200% Drive Rated Output Current
90% 8 “OutPowr 0-20” 18mA for 200% Drive Rated Power
A067 [Accel Time 2] Related Parameter(s): P039, A051-A054, A070-A077
A140-A147, E203-E206
When active, sets the rate of acceleration for all speed increases except jog.
Values Default: 20.0 Secs
Min/Max: 0.0/600.0 Secs
Display: 0.1 Secs
Maximum Freq
Accel Time
Accel Rate
=
Option
Description28 1
00Acc/Dec 1
01Acc/Dec 2
10Acc/Dec 3
11Acc/Dec 4
Speed
0
Time
P035 [Maximum Freq]
P039, A067,
E203 or E205
[Accel Time x]
P040, A068,
E204 or E206
[Decel Time x]
0
Acceleration
Deceleration
A068 [Decel Time 2] Related Parameter(s): P040, A051-A054, A067, A070-A077
A140-A147, E203-E206
When active, sets the rate of deceleration for all speed decreases except jog. Refer to graphic at A067
[Accel Time 2].
Values Default: 20.0 Secs
Min/Max: 0.0/600.0 Secs
Display: 0.1 Secs
Maximum Freq
Decel Time
Decel Rate
=

Table of Contents

Other manuals for Allen-Bradley PowerFlex 40P

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PowerFlex 40P and is the answer not in the manual?

Allen-Bradley PowerFlex 40P Specifications

General IconGeneral
BrandAllen-Bradley
ModelPowerFlex 40P
CategoryController
LanguageEnglish

Related product manuals